RP7400 Server - Specifications

Specifications
Physical
Description
Specifications
Dimensions (H, W, D)
35 x 19 x 17.5 in (81.2 x 48.2 x 44.5 cm)
Weight (configured)
Approximately 200 lbs (90 Kg)
Electrical
Description
Specifications
AC Input Power
100 or 240 VAC  50/60 Hz
Maximum Current Requirements
13.8 Amps at 220V
Maximum Power Dissipation
3000 Watts
Maximum Heat Dissipation
10,240 BTUs/Hour
Electromagnetic Interference
Complies with FCC Rules and Regulations, part 15, as a Class A digital device.  Manufacturer's Declaration to EN55022 Level A, VCCI Registered, Class I, Korea RLL.
Environmental
Description
Specifications
Sound power level
6.4 Bels LWA
Sound pressure level at operator position
58.2 dB LPA
Operating Altitude
To 3.0 km (10,000 ft) above sea level
Non Operating Altitude
To 4.5 km (15,000 ft) above sea level
Parameter
Maximum Non Operating Range
Recommended Range
Maximum Operating Range
Rate of Change (per hour)
Temperature
-40º to +65º C
(-40º to 149º F)
20º to 25º C
(70º to 77º F)
5º C to 35º C
(plus or minus 2º C)
(41º to 95º F
(plus or minus 3º F))
20º C (68º F)
Operating Humidity
5% to 90%, non-condensing at 25º C (77º F)
15 % to 80% non-condensing at 25º C (77º F)
15% to 80% non-condensing at 25º C (77º F)
30% RH/hour

hp-feedback-input-portlet

Actions
Loading...

hp-online-communities-portlet

Actions
Loading...

Ask the community!


Support Forum

Support Forum

Join the conversation! Find Solutions, ask questions, and share advice with other HP product owners. Visit now


hp-feedback-banner-portlet

Actions
Loading...

hp-country-locator-portlet

Actions
Loading...
United States

hp-detect-load-my-device-portlet

Actions
Loading...